← Backflow review queue
Backflow assembly test · 2200 Turkey Hill Way
ApprovedFiled Feb 18, 2025 by Taylor Whitcomb, Ridge Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Feb 18, 2025
- Assembly type
- RP
- Serial number
- K440439
- Size
- 1
- Test gauge serial
- G-3198
- Gauge calibration date
- Jun 23, 2024
- Check valve 1
- 6.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Relief valve opened at
- 2.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-56-01058
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2200 Turkey Hill Way
Owner: Morgan Stroud
Parcel 097-56-01058