← Backflow review queue
Backflow assembly test · 7472 Meadow Lark Trl
ApprovedFiled Mar 22, 2024 by Taylor Whitcomb, Ridge Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Mar 22, 2024
- Assembly type
- RP
- Serial number
- B705391
- Size
- 3/4
- Test gauge serial
- G-7353
- Gauge calibration date
- Nov 27, 2023
- Check valve 1
- 7.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 2.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 097-22-01031
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
7472 Meadow Lark Trl
Owner: Casey Hollins
Parcel 097-22-01031