← Backflow review queue
Backflow assembly test · Golden Taqueria
Needs reviewFiled Nov 19, 2026 by Jamie Hollins, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Nov 19, 2026
- Assembly type
- RP
- Serial number
- B732852
- Size
- 1 1/2
- Test gauge serial
- G-3284
- Gauge calibration date
- May 26, 2026
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 2.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 095-89-01110
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Property
6020 Meadow Lark Ct
Owner: Whitcomb Holdings LLC
Parcel 095-89-01110