Solano County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Golden Taqueria

Approved

Filed Nov 10, 2024 by Drew Nguyen, Valley Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Nov 10, 2024
Assembly type
RP
Serial number
W657557
Size
2
Test gauge serial
G-9461
Gauge calibration date
Mar 16, 2024
Check valve 1
7.4 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 095-64-01039
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

3845 Sycamore Dr
Owner: Vance Holdings LLC
Parcel 095-64-01039