Backflow assembly test · Golden Pizza
ApprovedFiled Nov 13, 2025 by Drew Vance, Northstar Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 13, 2025
- Assembly type
- RP
- Serial number
- B393674
- Size
- 1 1/2
- Test gauge serial
- G-8511
- Gauge calibration date
- Oct 9, 2025
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 2.3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 093-52-01041
- Readings in range, no flags
- Result: passing. Next due date resets when approved.