Backflow assembly test · 1201 Meadow Lark Ct
ApprovedFiled Sep 14, 2023 by Hayden Whitcomb, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 14, 2023
- Assembly type
- DC
- Serial number
- B734108
- Size
- 1
- Test gauge serial
- G-2998
- Gauge calibration date
- Dec 12, 2022
- Check valve 1
- 0.7 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 085-35-01317
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.