Backflow assembly test · 2868 Cedar Hollow Ct
ApprovedFiled Oct 18, 2024 by Reese Calloway, Clearwater Backflow Testing · filed from phone
Report
- Date of service
- Oct 18, 2024
- Assembly type
- RP
- Serial number
- B226563
- Size
- 3/4
- Test gauge serial
- G-6807
- Gauge calibration date
- Nov 30, 2023
- Check valve 1
- 0.1 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 3.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 085-36-01305
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.