Backflow assembly test · Main Street Animal Hospital
ApprovedFiled Mar 21, 2026 by Cameron Nguyen, Clearwater Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Mar 21, 2026
- Assembly type
- RP
- Serial number
- Z235664
- Size
- 1
- Test gauge serial
- G-9175
- Gauge calibration date
- Jan 3, 2026
- Check valve 1
- 7.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 085-10-01312
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.