Santa Barbara County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Market

Approved

Filed Jan 4, 2026 by Parker Vance, Keystone Backflow Testing · filed from phone

Report

Date of service
Jan 4, 2026
Assembly type
RP
Serial number
A284276
Size
1 1/2
Test gauge serial
G-6346
Gauge calibration date
Sep 29, 2025
Check valve 1
4 psid
Check valve 1 closed tight
Yes
Check valve 2
3.1 psid
Relief valve opened at
3.6 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 083-63-01051
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4951 Sycamore Rd
Owner: Whitcomb Holdings LLC
Parcel 083-63-01051