← Backflow review queue
Backflow assembly test · 278 Quarry Trl
ApprovedFiled Mar 13, 2026 by Reese Ashby, Keystone Backflow Testing · filed from phone
Report
- Date of service
- Mar 13, 2026
- Assembly type
- RP
- Serial number
- Z823078
- Size
- 3/4
- Test gauge serial
- G-4796
- Gauge calibration date
- Aug 10, 2025
- Check valve 1
- 8.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 083-41-01045
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
278 Quarry Trl
Owner: Cameron Kessler
Parcel 083-41-01045