Backflow assembly test · 4597 Hickory Way
ApprovedFiled May 10, 2026 by Parker Vance, Keystone Backflow Testing · filed from phone
Report
- Date of service
- May 10, 2026
- Assembly type
- RP
- Serial number
- W954378
- Size
- 1
- Test gauge serial
- G-1356
- Gauge calibration date
- Feb 9, 2026
- Check valve 1
- 6.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Relief valve opened at
- 2.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 083-62-01081
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4597 Hickory Way
Owner: Cameron Fairley
Parcel 083-62-01081