← Backflow review queue
Backflow assembly test · Hilltop Grill
ApprovedFiled Nov 12, 2026 by Parker Okafor, Summit Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Nov 12, 2026
- Assembly type
- RP
- Serial number
- K451241
- Size
- 1
- Test gauge serial
- G-5861
- Gauge calibration date
- May 16, 2026
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 2.7 psid
- Relief valve opened at
- 2.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-12-01296
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7822 Turkey Hill Trl
Owner: Fairley Holdings LLC
Parcel 079-12-01296