Backflow assembly test · 7111 Hickory Ln
ApprovedFiled Apr 14, 2025 by Sam Vance, Ridge Backflow Testing · paper form read in and confirmed by staff
Report
- Date of service
- Apr 14, 2025
- Assembly type
- RP
- Serial number
- Z281950
- Size
- 3/4
- Test gauge serial
- G-6185
- Gauge calibration date
- Feb 19, 2024
- Check valve 1
- 0.4 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.4 psid
- Relief valve opened at
- 2.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-24-01146
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7111 Hickory Ln
Owner: Sam Benton
Parcel 079-24-01146