Backflow assembly test · 2852 Ridgeview Dr
ApprovedFiled Dec 22, 2024 by Parker Okafor, Summit Backflow Testing · filed from phone
Report
- Date of service
- Dec 22, 2024
- Assembly type
- RP
- Serial number
- Z854367
- Size
- 3/4
- Test gauge serial
- G-2145
- Gauge calibration date
- Sep 9, 2023
- Check valve 1
- 0.3 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 2.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-70-01194
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2852 Ridgeview Dr
Owner: Casey Ellery
Parcel 079-70-01194