Backflow assembly test · 2626 Sycamore Ln
ApprovedFiled Dec 13, 2025 by Sam Vance, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Dec 13, 2025
- Assembly type
- RP
- Serial number
- B345539
- Size
- 3/4
- Test gauge serial
- G-3420
- Gauge calibration date
- May 30, 2025
- Check valve 1
- 4.2 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-51-01276
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
2626 Sycamore Ln
Owner: Jamie Okafor
Parcel 079-51-01276