Backflow assembly test · 6255 Laurel Rd
ApprovedFiled Mar 23, 2025 by Parker Okafor, Summit Backflow Testing · filed from phone
Report
- Date of service
- Mar 23, 2025
- Assembly type
- RP
- Serial number
- A883786
- Size
- 3/4
- Test gauge serial
- G-4071
- Gauge calibration date
- Feb 17, 2025
- Check valve 1
- 6.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.8 psid
- Relief valve opened at
- 3.9 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-90-01063
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
6255 Laurel Rd
Owner: Logan Whitcomb
Parcel 079-90-01063