← Backflow review queue
Backflow assembly test · 9625 Laurel Rd
ApprovedFiled Dec 1, 2024 by Parker Okafor, Summit Backflow Testing · filed from phone
Report
- Date of service
- Dec 1, 2024
- Assembly type
- RP
- Serial number
- A674665
- Size
- 3/4
- Test gauge serial
- G-7741
- Gauge calibration date
- Jul 31, 2023
- Check valve 1
- 5.6 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 1.2 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 079-90-01161
- RP relief valve must open at 2.0 psid or more.
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
9625 Laurel Rd
Owner: Hayden Ellery
Parcel 079-90-01161