← Backflow review queue
Backflow assembly test · 4119 Orchard Rd
ApprovedFiled Jul 2, 2025 by Casey Lindqvist, Heritage Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jul 2, 2025
- Assembly type
- RP
- Serial number
- W812082
- Size
- 1
- Test gauge serial
- G-9727
- Gauge calibration date
- Apr 23, 2025
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.4 psid
- Relief valve opened at
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 077-23-01263
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4119 Orchard Rd
Owner: Logan Brandt
Parcel 077-23-01263