San Francisco County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Two Rivers Grill

Approved

Filed Aug 11, 2026 by Alex Wexler, Heritage Backflow Testing · filed from phone

Report

Date of service
Aug 11, 2026
Assembly type
RP
Serial number
W156366
Size
4
Test gauge serial
G-7705
Gauge calibration date
Apr 6, 2026
Check valve 1
8.8 psid
Check valve 1 closed tight
Yes
Check valve 2
3.9 psid
Relief valve opened at
3.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 075-87-01257
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5998 Old Church Dr
Owner: Wexler Holdings LLC
Parcel 075-87-01257