Backflow assembly test · 2633 Cedar Hollow Ln
ApprovedFiled Nov 13, 2024 by Blake Pruitt, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Nov 13, 2024
- Assembly type
- PVB
- Serial number
- Z427319
- Size
- 3/4
- Test gauge serial
- G-8149
- Gauge calibration date
- Oct 7, 2024
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 075-12-01180
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
2633 Cedar Hollow Ln
Owner: Taylor Brandt
Parcel 075-12-01180