Backflow assembly test · Maple Leaf Apartments
ApprovedFiled Mar 11, 2025 by Jordan Wexler, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 11, 2025
- Assembly type
- RP
- Serial number
- K565354
- Size
- 1 1/2
- Test gauge serial
- G-7712
- Gauge calibration date
- Jan 26, 2024
- Check valve 1
- 0.2 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 075-75-01340
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
5922 Hickory Ln
Owner: Hollins Holdings LLC
Parcel 075-75-01340