San Francisco County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Pizza

Approved

Filed Mar 29, 2025 by Blake Pruitt, Patriot Plumbing & Backflow · paper form read in and confirmed by staff

Report

Date of service
Mar 29, 2025
Assembly type
RP
Serial number
A270474
Size
2
Test gauge serial
G-4813
Gauge calibration date
Dec 10, 2024
Check valve 1
7.5 psid
Check valve 1 closed tight
Yes
Check valve 2
1.2 psid
Relief valve opened at
3.2 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 075-50-01074
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

5203 Mill Creek Dr
Owner: Marsh Holdings LLC
Parcel 075-50-01074