← Backflow review queue
Backflow assembly test · Station Diner
ApprovedFiled Sep 4, 2025 by Jordan Wexler, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Sep 4, 2025
- Assembly type
- RP
- Serial number
- B768749
- Size
- 1 1/2
- Test gauge serial
- G-8001
- Gauge calibration date
- Nov 15, 2024
- Check valve 1
- 5.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.9 psid
- Relief valve opened at
- 3.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 075-20-01029
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
8344 Mill Creek Trl
Owner: Ramirez Holdings LLC
Parcel 075-20-01029