Backflow assembly test · Station Pizza

Approved

Filed Oct 7, 2026 by Logan Vance, Ridge Backflow Testing · filed from phone

Report

Date of service
Oct 7, 2026
Assembly type
RP
Serial number
B623069
Size
2
Test gauge serial
G-9269
Gauge calibration date
Jun 30, 2025
Check valve 1
0.4 psid
Check valve 1 closed tight
No
Check valve 2
3.9 psid
Relief valve opened at
2.5 psid
Result
Fail
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 073-54-01218
  • Test gauge calibration is more than a year old.
  • Result: needs follow-up. The property stays on the overdue list until a passing report arrives.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7121 Hickory Ln
Owner: Danner Holdings LLC
Parcel 073-54-01218