Backflow assembly test · 4623 Fox Run Way
ApprovedFiled May 20, 2026 by Parker Fairley, Heritage Backflow Testing · filed from phone
Report
- Date of service
- May 20, 2026
- Assembly type
- DC
- Serial number
- K953317
- Size
- 3/4
- Test gauge serial
- G-4520
- Gauge calibration date
- Sep 29, 2025
- Check valve 1
- 7.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 073-43-01352
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4623 Fox Run Way
Owner: Riley Ramirez
Parcel 073-43-01352