Backflow assembly test · 5878 Turkey Hill Way
ApprovedFiled Aug 7, 2025 by Drew Hollins, Summit Backflow Testing · filed from phone
Report
- Date of service
- Aug 7, 2025
- Assembly type
- PVB
- Serial number
- W306575
- Size
- 3/4
- Test gauge serial
- G-8577
- Gauge calibration date
- Feb 7, 2025
- Check valve 1
- 3.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 071-49-01267
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.