Fire protection system inspection · Station Brewing Co
ApprovedFiled Aug 22, 2025 by Alex Brandt, Ridge Fire Protection · filed from phone
Report
- Date of service
- Aug 22, 2025
- System
- Wet sprinkler
- Inspected to
- NFPA 25
- Result
- Impairment
- Impairment: describe and who was notified
- Main control valve leaking; fire department and owner notified
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for fire sprinkler contractor
- All required fields present
- Address matches parcel 071-83-01072
- Impairment reported: the fire marshal should be notified the same day.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
4184 Quarry Dr
Owner: Calloway Holdings LLC
Parcel 071-83-01072