← Backflow review queue
Backflow assembly test · 6903 Turkey Hill Way
ApprovedFiled Dec 3, 2023 by Quinn Wexler, Lakeside Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Dec 3, 2023
- Assembly type
- RP
- Serial number
- W314985
- Size
- 3/4
- Test gauge serial
- G-6464
- Gauge calibration date
- Oct 2, 2023
- Check valve 1
- 7.7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.5 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 067-10-01118
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
6903 Turkey Hill Way
Owner: Logan Ellery
Parcel 067-10-01118