Sacramento County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Main Street Diner

Approved

Filed Apr 12, 2024 by Emerson Stroud, Keystone Plumbing & Backflow · filed from phone

Report

Date of service
Apr 12, 2024
Assembly type
DC
Serial number
A890451
Size
4
Test gauge serial
G-7999
Gauge calibration date
Aug 4, 2023
Check valve 1
6.3 psid
Check valve 1 closed tight
Yes
Check valve 2
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 067-40-01099
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.

Property

7496 Fox Run Way
Owner: Ellery Holdings LLC
Parcel 067-40-01099