Backflow assembly test · 2499 Spring Branch Dr
ApprovedFiled Apr 30, 2025 by Reese Danner, Keystone Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 30, 2025
- Assembly type
- RP
- Serial number
- A987812
- Size
- 1
- Test gauge serial
- G-1983
- Gauge calibration date
- Dec 16, 2024
- Check valve 1
- 5.4 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.3 psid
- Relief valve opened at
- 3.8 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 067-97-01012
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.