Backflow assembly test · 5614 Fox Run Dr
ApprovedFiled Dec 13, 2023 by Quinn Nguyen, Valley Plumbing & Backflow · filed from phone
Report
- Date of service
- Dec 13, 2023
- Assembly type
- DC
- Serial number
- A260259
- Size
- 3/4
- Test gauge serial
- G-8844
- Gauge calibration date
- Oct 26, 2023
- Check valve 1
- 3.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 2.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 065-72-01102
- Readings in range, no flags
- Result: passing. Next due date resets when approved.