Riverside County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Grill

Approved

Filed Sep 2, 2026 by Parker Okafor, Valley Plumbing & Backflow · filed from phone

Report

Date of service
Sep 2, 2026
Assembly type
RP
Serial number
K448398
Size
2
Test gauge serial
G-1109
Gauge calibration date
Nov 13, 2025
Check valve 1
5 psid
Check valve 1 closed tight
Yes
Check valve 2
2.8 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 065-82-01359
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

6053 Stone Gate Trl
Owner: Ramirez Holdings LLC
Parcel 065-82-01359