Backflow assembly test · 899 Spring Branch Rd
ApprovedFiled Jul 1, 2025 by Jamie Kessler, Valley Backflow Testing · filed from phone
Report
- Date of service
- Jul 1, 2025
- Assembly type
- DC
- Serial number
- K730340
- Size
- 3/4
- Test gauge serial
- G-5139
- Gauge calibration date
- May 13, 2024
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 1.1 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 061-10-01264
- Test gauge calibration is more than a year old.
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.