Backflow assembly test · Hilltop Animal Hospital
ApprovedFiled Aug 7, 2025 by Taylor Ashby, Valley Backflow Testing · filed from phone
Report
- Date of service
- Aug 7, 2025
- Assembly type
- RP
- Serial number
- A171109
- Size
- 1 1/2
- Test gauge serial
- G-5228
- Gauge calibration date
- Dec 13, 2024
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.5 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 061-51-01287
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
5642 Meadow Lark Way
Owner: Marsh Holdings LLC
Parcel 061-51-01287