← Backflow review queue
Backflow assembly test · 3078 Meadow Lark Rd
ApprovedFiled Feb 10, 2026 by Avery Calloway, Clearwater Plumbing & Backflow · filed from phone
Report
- Date of service
- Feb 10, 2026
- Assembly type
- RP
- Serial number
- A394491
- Size
- 3/4
- Test gauge serial
- G-2716
- Gauge calibration date
- Dec 25, 2025
- Check valve 1
- 4.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Relief valve opened at
- 3.2 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 061-26-01188
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.
Property
3078 Meadow Lark Rd
Owner: Rowan Danner
Parcel 061-26-01188