Backflow assembly test · 6000 Spring Branch Rd
ApprovedFiled Mar 10, 2026 by Taylor Ashby, Valley Backflow Testing · filed from phone
Report
- Date of service
- Mar 10, 2026
- Assembly type
- PVB
- Serial number
- K760468
- Size
- 3/4
- Test gauge serial
- G-9202
- Gauge calibration date
- Dec 4, 2024
- Check valve 1
- 9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.1 psid
- Result
- Repaired and passed
- Repairs made
- Replaced check valve 1 rubber
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 061-58-01282
- Test gauge calibration is more than a year old.
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.