Placer County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · Maple Leaf Grill

Approved

Filed Nov 6, 2025 by Taylor Ashby, Valley Backflow Testing · filed from phone

Report

Date of service
Nov 6, 2025
Assembly type
RP
Serial number
Z762457
Size
1
Test gauge serial
G-7930
Gauge calibration date
Sep 7, 2025
Check valve 1
8.2 psid
Check valve 1 closed tight
Yes
Check valve 2
2 psid
Relief valve opened at
2.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 061-10-01032
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

9501 Cedar Hollow Ln
Owner: Lindqvist Holdings LLC
Parcel 061-10-01032