Backflow assembly test · 5211 Turkey Hill Ln
ApprovedFiled Jul 14, 2025 by Avery Calloway, Clearwater Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 14, 2025
- Assembly type
- RP
- Serial number
- A216445
- Size
- 1
- Test gauge serial
- G-8454
- Gauge calibration date
- Jun 2, 2025
- Check valve 1
- 3.9 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.2 psid
- Relief valve opened at
- 2.7 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 061-95-01000
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.