← Backflow review queue
Backflow assembly test · Main Street Bakery
ApprovedFiled Aug 10, 2024 by Logan Stroud, Ridge Backflow Testing · filed from phone
Report
- Date of service
- Aug 10, 2024
- Assembly type
- DC
- Serial number
- A513528
- Size
- 1
- Test gauge serial
- G-7106
- Gauge calibration date
- Feb 21, 2024
- Check valve 1
- 8.8 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 059-53-01035
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
8390 Fox Run Trl
Owner: Ellery Holdings LLC
Parcel 059-53-01035