Backflow assembly test · Blue Heron Grill

Approved

Filed Apr 30, 2026 by Logan Stroud, Ridge Backflow Testing · filed from phone

Report

Date of service
Apr 30, 2026
Assembly type
RP
Serial number
A701356
Size
1
Test gauge serial
G-3128
Gauge calibration date
Nov 18, 2025
Check valve 1
6.6 psid
Check valve 1 closed tight
Yes
Check valve 2
4 psid
Relief valve opened at
1.6 psid
Result
Repaired and passed
Repairs made
Replaced check valve 1 rubber
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 059-63-01287
  • RP relief valve must open at 2.0 psid or more.
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.