Backflow assembly test · 3962 Quarry Ln
ApprovedFiled Mar 10, 2026 by Parker Brandt, Heritage Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 10, 2026
- Assembly type
- RP
- Serial number
- Z909166
- Size
- 3/4
- Test gauge serial
- G-4831
- Gauge calibration date
- Nov 1, 2025
- Check valve 1
- 0.6 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.7 psid
- Relief valve opened at
- 2.6 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 055-91-01035
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by J. Staff. The property's next due date is set and the owner gets a receipt.