Backflow assembly test · Crossroads Self Storage

Approved

Filed Nov 11, 2025 by Cameron Ellery, Northstar Plumbing & Backflow · filed from phone

Report

Date of service
Nov 11, 2025
Assembly type
DC
Serial number
Z946905
Size
1
Test gauge serial
G-4576
Gauge calibration date
Feb 15, 2025
Check valve 1
4.2 psid
Check valve 1 closed tight
Yes
Check valve 2
3.7 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 055-60-01016
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

4706 Mill Creek Ct
Owner: Ashby Holdings LLC
Parcel 055-60-01016