← Backflow review queue
Backflow assembly test · 6988 Stone Gate Ln
ApprovedFiled Aug 29, 2025 by Rowan Benton, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Aug 29, 2025
- Assembly type
- RP
- Serial number
- W212978
- Size
- 3/4
- Test gauge serial
- G-6058
- Gauge calibration date
- Jan 21, 2025
- Check valve 1
- 7.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 3.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 053-50-01328
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
6988 Stone Gate Ln
Owner: Drew Calloway
Parcel 053-50-01328