Backflow assembly test · 2923 Hickory Rd
ApprovedFiled Jul 26, 2026 by Parker Pruitt, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Jul 26, 2026
- Assembly type
- DC
- Serial number
- W324566
- Size
- 1
- Test gauge serial
- G-4568
- Gauge calibration date
- Jun 10, 2026
- Check valve 1
- 0.5 psid
- Check valve 1 closed tight
- No
- Check valve 2
- 3.9 psid
- Result
- Fail
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 053-92-01058
- Readings in range, no flags
- Result: needs follow-up. The property stays on the overdue list until a passing report arrives.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
2923 Hickory Rd
Owner: Rowan Kessler
Parcel 053-92-01058