Backflow assembly test · 2923 Hickory Rd
ApprovedFiled Jun 16, 2024 by Emerson Hollins, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Jun 16, 2024
- Assembly type
- DC
- Serial number
- W324566
- Size
- 1
- Test gauge serial
- G-4815
- Gauge calibration date
- Aug 30, 2023
- Check valve 1
- 4.5 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.6 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 053-92-01058
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.