← Backflow review queue
Backflow assembly test · 4100 Quarry Way
ApprovedFiled Jun 19, 2026 by Cameron Kessler, Summit Plumbing & Backflow · paper form read in and confirmed by staff
Report
- Date of service
- Jun 19, 2026
- Assembly type
- RP
- Serial number
- A336663
- Size
- 1
- Test gauge serial
- G-5018
- Gauge calibration date
- Feb 3, 2026
- Check valve 1
- 6.3 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 3.3 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 053-32-01353
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.
Property
4100 Quarry Way
Owner: Emerson Ramirez
Parcel 053-32-01353