Backflow assembly test · 3153 Turkey Hill Ln

Approved

Filed Oct 30, 2024 by Cameron Kessler, Summit Plumbing & Backflow · filed from phone

Report

Date of service
Oct 30, 2024
Assembly type
RP
Serial number
Z921430
Size
3/4
Test gauge serial
G-7766
Gauge calibration date
Feb 15, 2024
Check valve 1
5.9 psid
Check valve 1 closed tight
Yes
Check valve 2
1.8 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 053-15-01227
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by J. Staff. The property's next due date is set and the owner gets a receipt.

Property

3153 Turkey Hill Ln
Owner: Jamie Ashby
Parcel 053-15-01227