← Backflow review queue
Backflow assembly test · Hilltop Apartments
ApprovedFiled Mar 6, 2026 by Emerson Hollins, Patriot Plumbing & Backflow · filed from phone
Report
- Date of service
- Mar 6, 2026
- Assembly type
- RP
- Serial number
- B322578
- Size
- 4
- Test gauge serial
- G-2777
- Gauge calibration date
- Dec 11, 2025
- Check valve 1
- 7 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.6 psid
- Relief valve opened at
- 2.4 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 053-44-01130
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.
Property
7969 Laurel Dr
Owner: Ellery Holdings LLC
Parcel 053-44-01130