Backflow assembly test · Two Rivers Taqueria
ApprovedFiled Apr 13, 2026 by Rowan Benton, Summit Plumbing & Backflow · filed from phone
Report
- Date of service
- Apr 13, 2026
- Assembly type
- RP
- Serial number
- W399892
- Size
- 4
- Test gauge serial
- G-9351
- Gauge calibration date
- Feb 28, 2026
- Check valve 1
- 4.1 psid
- Check valve 1 closed tight
- Yes
- Check valve 2
- 1.5 psid
- Relief valve opened at
- 3.1 psid
- Result
- Pass
- I certify this report is true and that I performed or supervised the work
- Yes
Automatic checks
- License on file and current for backflow tester
- All required fields present
- Address matches parcel 053-91-01205
- Readings in range, no flags
- Result: passing. Next due date resets when approved.
Decision
Approved by Auto-approved (no flags). The property's next due date is set and the owner gets a receipt.