Mono County, CACompliance reporting portal
Demo · made-up dataOpen the pro appChange county
← Backflow review queue

Backflow assembly test · 8423 Meadow Lark Trl

Approved

Filed Oct 15, 2025 by Parker Nguyen, Heritage Backflow Testing · filed from phone

Report

Date of service
Oct 15, 2025
Assembly type
RP
Serial number
K662853
Size
1
Test gauge serial
G-4744
Gauge calibration date
Jul 27, 2025
Check valve 1
7.6 psid
Check valve 1 closed tight
Yes
Check valve 2
2.9 psid
Relief valve opened at
2.4 psid
Result
Pass
I certify this report is true and that I performed or supervised the work
Yes

Automatic checks

  • License on file and current for backflow tester
  • All required fields present
  • Address matches parcel 051-89-01029
  • Readings in range, no flags
  • Result: passing. Next due date resets when approved.

Decision

Approved by M. Reviewer. The property's next due date is set and the owner gets a receipt.

Property

8423 Meadow Lark Trl
Owner: Hayden Lindqvist
Parcel 051-89-01029